Short answer: Ethernet's standard copper channel is 100 m (328 ft) — 90 m of solid-core horizontal cable plus 10 m of patch cords, the channel defined by TIA-568 and ISO/IEC 11801 and used by IEEE 802.3 PHYs through 10GBASE-T. The exceptions are Cat6 at 10GBASE-T (up to 55 m, often 37–55 m depending on alien crosstalk) and Cat8 at 25/40GBASE-T (30 m).
| Cable | 1 Gbps | 2.5 / 5 Gbps | 10 Gbps | 25 / 40 Gbps |
|---|---|---|---|---|
| Cat5e | 100 m | 100 m* | Not specified | Not specified |
| Cat6 | 100 m | 100 m | up to 55 m (often 37–55 m) | Not specified |
| Cat6a | 100 m | 100 m | 100 m | Not specified |
| Cat7 (ISO Class F) | 100 m | 100 m | 100 m | Not specified |
| Cat8 | 30 m channel | 30 m channel | 30 m channel | 30 m |
*5GBASE-T over Cat5e is installation-dependent because alien crosstalk is not specified for Cat5e; Cat6 or better is recommended. Cat7 is an ISO/IEC Class F system, not a TIA-recognised category.
Ethernet Distance Calculator
Calculated Limits
100 m
328.1 ft
74%
14.3 dB
~0.22 dB/m model
65%
Signal Visualization
The graph and eye diagram update live with your inputs and stay synchronized with the link status.
Distance & Attenuation Curve
Signal Eye Diagram
OPEN EYEA wide-open eye means a clean, reliable signal. A collapsed eye with noise and error dots means the run is beyond its certified limit.
Where the 100 m Channel Comes From
The 100 m figure is a cabling-channel limit, not an IEEE PHY invention. TIA-568 and ISO/IEC 11801 define a horizontal channel as up to 90 m of solid-core permanent-link cable plus 10 m total of patch and equipment cords. The permanent link is what is installed in the wall and certified; the channel is what the network actually uses. A 100 ft (30.5 m) patch cord is three times the entire 10 m cord allowance of a 100 m channel — it is not a "long horizontal run", it is a patch cord, and it exhausts the cord budget several times over before it reaches the wall outlet.
IEEE 802.3 then specifies its BASE-T PHYs against that channel: 10BASE-T, 100BASE-TX and 1000BASE-T are specified to 100 m over the appropriate cabling, and 10GBASE-T uses 100 m over Cat6a (and up to 55 m over Cat6). The split exists because stranded patch cord has higher attenuation than solid horizontal cable; the 10 m cord allowance is a budget, not a target. Design horizontal pulls at 90 m or less so the patch cords still fit.
For the subnetting side of the same network, the CIDR chart maps every prefix to its mask and usable host count. The subnet calculator works through the host range for a specific prefix, and the IP range calculator converts a first-to-last address range into CIDR blocks. If you are configuring the gateway at the far end of the run, the default gateway calculator shows how the first usable address is chosen.
Cat6 at 10GBASE-T: Up to 55 m, Often 37–55 m
Cat6 handles 1 Gbps to 100 m, but 10GBASE-T is a much harder PHY: four pairs, roughly 400–500 MHz of signalling and a tight noise budget. Internal crosstalk inside the cable is controlled by the Cat6 specification; alien crosstalk (ANEXT) from neighbouring cables is not. That is why IEEE 802.3an specifies 10GBASE-T over Cat6 to up to 55 m, not 100 m.
TIA TSB-155 is more precise about installed cabling: 10GBASE-T should operate over Cat6 channels up to 37 m, and over channels between 37 and 55 m depending on the alien-crosstalk environment; lengths above 55 m may require mitigation. In a dense, tightly bundled tray, treat 37 m as the safer design target. In a clean, well-spaced installation, 55 m may test clean. Cat6a is the TIA category specified for 10GBASE-T to the full 100 m channel.
The practical rule: if a 10GBASE-T run must be reliable at 100 m, specify Cat6a (or Cat7/Class F in an ISO/IEC project). Do not describe a Cat6 installation as "certified to 55 m" without qualification — 55 m is the standard's upper bound, and TSB-155 makes the actual number installation-dependent.
Cat5e, Cat6, Cat6a, Cat7 and Cat8 Compared
| Category | Bandwidth | Standard | Certified channel | Notes |
|---|---|---|---|---|
| Cat5e | 100 MHz | TIA-568.2-D | 100 m | 1GBASE-T at 100 m; 2.5G/5G per 802.3bz, with 5G installation-dependent. |
| Cat6 | 250 MHz | TIA-568.2-D | 100 m (1G/2.5G/5G); 55 m upper bound at 10G | 10GBASE-T often 37–55 m depending on alien crosstalk (TSB-155). |
| Cat6a | 500 MHz | TIA-568.2-D | 100 m | TIA category specified for 10GBASE-T to 100 m. |
| Cat7 | 600 MHz | ISO/IEC 11801 Class F | 100 m | Not recognised by TIA-568; often GG45/TERA connectors, not RJ45. |
| Cat8 | 2000 MHz | TIA-568.2-D / ISO Class I–II | 30 m | Specified for 25GBASE-T and 40GBASE-T (IEEE 802.3bq); data-centre use. |
Cat7 is the category that causes the most confusion in TIA-568 projects. It is a real ISO/IEC Class F specification, but TIA-568 does not recognise it and goes from Cat6a directly to Cat8. If your specification cites TIA-568, Cat7 is not a compliant category to quote, even if the cable is sold as "Cat7".
2.5GBASE-T and 5GBASE-T on Existing Cable
IEEE 802.3bz defines 2.5GBASE-T and 5GBASE-T for Cat5e and Cat6 at up to 100 m. 2.5GBASE-T is the more forgiving of the two. 5GBASE-T uses roughly twice the bandwidth and is more sensitive to alien crosstalk, which Cat5e was never specified to control. A clean, unbundled Cat5e run may carry 5 Gbps at 100 m; a tight bundle in a warm ceiling may not.
TIA TSB-5021 gives installation guidance for 2.5G/5G over existing cabling, and the practical recommendation is the same one the standards make: Cat6 or Cat6a for new 5GBASE-T links, Cat5e only when the installation has been assessed. The calculator above shows 100 m for Cat5e at 5 Gbps but adds the certification caveat so the number is not mistaken for a guarantee.
Extending Ethernet Beyond 100 Metres
When a run needs to go farther than the certified channel, you have three practical options. Each one keeps every individual copper segment inside its own limit:
- 1.Active PoE extenders — a powered unit regenerates the Ethernet signal and can re-power PoE devices. Vendors commonly quote about 200–300 m in two 100 m hops; the exact figure is product-dependent and not an IEEE distance.
- 2.Inline or industrial switches — placed at the 90–100 m mark, the switch terminates one segment and starts a fresh one. Each copper segment stays inside its certified limit, and you gain extra ports.
- 3.Fibre media converters — convert the copper port to multimode or singlemode fibre. Fibre distances depend on the optic and fibre type, from a few hundred metres to tens of kilometres, and are outside the copper channel rule.
Whatever method you choose, the rule does not change: no single copper segment may exceed its certified channel length. For PoE budgeting on the new segment, use the PoE budget calculator; for the fibre side, the fibre loss budget calculator checks the optical power budget.
A Note on CCA Cable
Bargain "Cat6" and "Cat7" cables are sometimes copper-clad aluminium (CCA) or copper-clad steel (CCS). ANSI/TIA-568.2-D requires copper conductors for category cable; CCA is not a compliant substitute. (Some fire-rating listings for CM/CMR/CMP cable also assume copper conductors, but verify the listing on the specific reel.) Aluminium has roughly 50–60% higher resistance than copper of the same gauge, which increases DC voltage drop and heat on PoE runs. If a bulk cable is suspiciously cheap, check the jacket marking and ask for the conductor declaration before pulling it.
Sources
Every external distance claim on this page is listed below with the standard it comes from and the public source used. "Standard page" links point at the standard itself (IEEE Xplore); "Secondary reference" links are vendor or educational articles that explain the standard.
| Claim / Standard | Source | Type |
|---|---|---|
100 m channel = 90 m horizontal cable + 10 m patch cords ANSI/TIA-568.2-D; ISO/IEC 11801-1 | Wikipedia: ANSI/TIA-568 | Secondary reference |
10GBASE-T: Cat6 up to 55 m, Cat6a up to 100 m IEEE 802.3an-2006 | IEEE Xplore: 802.3an-2006 | Standard page |
Cat6 10GBASE-T: 37–55 m depending on alien crosstalk TIA TSB-155 | Fluke: 10GBASE-T field testing | Secondary reference |
Cat7 is ISO/IEC 11801 Class F, not a TIA-recognised category ISO/IEC 11801-1 | Wikipedia: ISO/IEC 11801 | Secondary reference |
2.5GBASE-T and 5GBASE-T run to 100 m; Cat5e 5G depends on alien crosstalk IEEE 802.3bz-2016; TIA TSB-5021 | IEEE Xplore: 802.3bz-2016 | Standard page |
25GBASE-T and 40GBASE-T are specified for 30 m channels over Cat8 IEEE 802.3bq-2016 | IEEE Xplore: 802.3bq-2016 | Standard page |
PoE bundle temperature rise and derating guidance TIA TSB-184-A | Belden: TSB-184-A | Secondary reference |
Cat8 cabling uses a 30 m channel even at lower speeds ANSI/TIA-568.2-D; ISO/IEC 11801-1 | Fluke: Category 8 testing | Secondary reference |
As an Amazon Associate I earn from qualifying purchases. Prices and availability are accurate as of the time of writing.
Frequently Asked Questions
What is the maximum length for an Ethernet cable?
The standard copper Ethernet channel is 100 m (328 ft): 90 m of solid-core horizontal cable plus 10 m of patch cords, the channel defined by TIA-568 and ISO/IEC 11801 and used by IEEE 802.3 PHYs through 10GBASE-T. The two important exceptions are Cat6 at 10GBASE-T (up to 55 m, often 37–55 m depending on alien crosstalk) and Cat8 at 25/40GBASE-T (30 m).
Why does Cat6 10GBASE-T drop to 55 m?
Alien crosstalk (ANEXT) from neighbouring cables becomes the dominant noise source at 10GBASE-T frequencies. IEEE 802.3an sets the Cat6 limit at 55 m, and TIA TSB-155 says 10GBASE-T should operate up to 37 m and between 37 and 55 m depending on the alien-crosstalk environment. Cat6a is the TIA category specified for 10GBASE-T to the full 100 m channel.
Is Cat7 a TIA-recognised category?
No. Cat7 is defined by ISO/IEC 11801 as Class F (600 MHz) and is not recognised by TIA-568, which goes from Cat6a to Cat8. Cat7 can carry 10GBASE-T over a 100 m channel, but it is an ISO/IEC Class F system, often with GG45 or TERA connectors rather than RJ45. For a TIA-568 project, specify Cat6a or Cat8.
Does 5GBASE-T really run on Cat5e at 100 m?
IEEE 802.3bz specifies 2.5GBASE-T and 5GBASE-T over Cat5e and Cat6 at up to 100 m, but 5GBASE-T margin on Cat5e depends on alien crosstalk, bundle size and installation quality. TIA TSB-5021 treats Cat5e 5GBASE-T as installation-dependent; Cat6 or Cat6a is the safer choice for new 5 Gbps links.
Does Power over Ethernet reduce the maximum cable distance?
PoE does not change the 100 m data-channel limit, because power is carried in common mode on the same pairs. Long runs still lose DC voltage, and current through the cable raises bundle temperature, which increases insertion loss. TIA TSB-184-A gives bundle-size and temperature-rise guidance for PoE, PoE+ and PoE++; it does not extend the data distance.
Can I extend Ethernet beyond 100 metres?
Yes, but not by pulling a longer single copper segment. Use an active extender that regenerates the signal (commonly quoted at about 200–300 m in two hops, vendor-dependent), an inline or industrial switch that starts a fresh 100 m segment, or fibre media converters for long runs. Every copper segment must stay inside its own certified channel limit.